Capacity | Fuel | Regulation |
---|---|---|
4600kw to 6600 kw | Light Oil | HIGH/LOW and Modulating |
The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW.
The PO Series burner is commonly used on large industrial steam and hot water boilers.
Key Features:
• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control
All P series burners are design and manufactured in accordance with EN267 and EN676
Model PO | 250/5.1 | 250/5.5 | 250/6.0 | 250/6.2 | 250/6.6 | 250/7.0 | 250/7.3 |
Output (nett CV) MW | 4.6 | 5.4 | 5.4 | 5.6 | 5.9 | 6.3 | 6.6 |
Fan Size Kw | 11 | 11 | 11 | 11 | 11 | 15 | 15 |
Pump Motor | |||||||
(Distillate Fuel Kw | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 |
Pump Motor | |||||||
(Residuel Fuel) Kw | 1.5 | 1.5 | 1.5 | 3.0 | 3.0 | 3.0 | 3.0 |
Pre-heater | |||||||
(Residual Fuel Only) Kw | 24 | 24 | 24 | 30 | 30 | 30 | 36 |
Electrical Supply V/Hz | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 |
Oil Inlet Pressure psi | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 |
Fuel Pump | KSA 1600/T3 | KSA 1600/T3 | KSA 1600/T3 | KSA 1600/T3 | KSA 1600/T3 | KSA 1600/T3 | KSA 1600/T3 |
Operation | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating |
Control Unit | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 |
Turndown | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 |
Flame Monitor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor |
Flame Tube Lengths mm | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 |
Noise dBA | 93 | 93 | 93 | 93 | 93 | 93 | 93 |
Nox mg/kWh | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 |
CO mg/kWh | ‹110 | ‹110 | ‹110 | ‹110 | ‹110 |