PDF 250
Capacity | Fuel | Regulation |
---|---|---|
4.6-6.6 MW | LPG/ NG/ Biogas | ON/OFF, HIGH/LOW and Modulating |
The PDF Series burner can operate on gas (NG, LPG, Towns Gas and Biogas), oil (Class D light oil, Class G HFO) or a dual fuel combination and is available in standard outputs from 3.3MW to 18MW.
The PDF Series burner is commonly used on large industrial steam and hot water boilers.
Key Features:
Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
Low NOx Head
Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
Variable Speed Drive (VSD) combustion air fan motor
Air inlet silencer (< 85dBA)
Oxygen trim for improved efficiency and reduced emissions
Separate or integrated water level controls for steam boilers
Data Transfer Interface for BMS control
All P series burners are design and manufactured in accordance with EN267 and EN676.
Model PDF | 250/5.1 | 250/5.5 | 250/6.0 | 250/6.2 | 250/6.6 | 250/7.0 | 250/7.3 | |
Output (nett CV) | MW | 4.6 | 5.5 | 5.4 | 5.6 | 5.9 | 6.3 | 6.6 |
Fan Size | kW | 11 | 11 | 11 | 11 | 11 | 15 | 15 |
Pump Motor (Distillate Fuel) | kW | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 |
Pump Motor (Residual Fuel) | kW | 1.5 | 1.5 | 1.5 | 3.0 | 3.0 | 3.0 | 3.0 |
Pre-heater (Residual Fuel only) | kW | 24 | 24 | 24 | 30 | 30 | 30 | 36 |
Electrical Supply | V/Hz | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 |
Oil inlet pressure | psi | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 |
Gas inlet pressure (min/max) | mbar | 140/300 | 140/300 | 140/300 | 140/300 | 140/300 | 140/300 | 140/300 |
Gas train inlet conn. |
| PN16 DN80 | PN16 DN80 | PN16 DN80 | PN16 DN80 | PN16 DN80 | PN16 DN80 | PN16 DN80 |
Operation |
| Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating |
Control Unit |
| Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 |
Gas Turndown |
| up to 7.0 | up to 7.0 | up to 7.0 | up to 7.0 | up to 7.0 | up to 7.0 | up to 7.0 |
Oil Turndown |
| up to 4.0 | up to 4.0 | up to 4.0 | up to 4.0 | up to 4.0 | up to 4.0 | up to 4.0 |
Flame Monitor |
| UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor |
Flame tube lengths | mm | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 |
GAS |
|
|
|
|
|
|
|
|
Noise | dBA | 93 | 93 | 93 | 93 | 93 | 93 | 93 |
NOx | mg/kWh | 140-190 | 140-190 | 140-190 | 140-190 | 140-190 | 140-190 | 140-190 |
OIL |
|
|
|
|
|
|
|
|
Noise | dBA | 93 | 93 | 93 | 93 | 93 | 93 | 93 |
NOx | mg/kWh | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 |
CO | mg/kWh | <110 | <110 | <110 | <110 | <110 | <110 | <110 |